flash_on
100% Canadian Owned and Operated – Shipping across Canada and America – 24*7 Emergency Services

Eaton A200 A200MACX NEMA Size 00 Non-Reversing Starter 2HP 480V 480V 60Hz Coil

star
star
star
star
star

Size 00, Non Rev, Starter, 2HP, 600V, OLR FH heater elements ordered separately (V5-T2-136/137)

Part Number:
Warranty:
In Stock
Available
Part Number
A200MACX
Manufacturer
Eaton
Current Rating
9
Voltage Rating (V)
600
Number of Poles
3
Weight
3.5 lb shipping weight
Dimensions
3.31 W x 6.42 H x 4.61 D in
Standards Compliance
UL 508 (UL listed), CSA certified
UL Listed
Yes
Contact Configuration and Auxiliary
3NO; 1NO holding circuit interlock
Disconnect and Short Circuit Protection
No; Not included - fuses or inverse-time breaker per NEC 430 Part D
Starter Type
Full voltage magnetic with Type B block overload (ambient compensated, manual reset)
HP Rating
1-ph: 1/3 HP @115V, 1 HP @230V; 3-ph: 1-1/2 HP @208V, 1-1/2 HP @240V, 2 HP @480V, 2 HP @600V
Voltage Rating V
600
Number of Phases
3
NEMA Size
0
Overload Range A
FH heater elements ordered separately (V5-T2-136/137)
Overload Class
Class 20 (Type B, manual reset)
Coil Voltage
480V 60Hz
Enclosure Type NEMA
Open
Reversing
No
Standards Compliance
UL 508 (UL listed), CSA certified
Application Use Case
Industrial motor control: pumps, fans, compressors, conveyors and machinery
Special Features
Type B ambient compensated overload relay

Eaton A200 A200MACX NEMA Size 00 Non-Reversing Starter 2HP 480V 480V 60Hz Coil

The Eaton A200 A200MACX NEMA Size 00 Non-Reversing Starter 2HP 480V 480V 60Hz Coil is part of Eaton's A200 NEMA motor control line.

Technical Specifications

  • Contact Configuration and Auxiliary: 3NO; 1NO holding circuit interlock
  • Disconnect and Short Circuit Protection: No; Not included - fuses or inverse-time breaker per NEC 430 Part D
  • Starter Type: Full voltage magnetic with Type B block overload (ambient compensated, manual reset)
  • HP Rating: 1-ph: 1/3 HP @115V, 1 HP @230V; 3-ph: 1-1/2 HP @208V, 1-1/2 HP @240V, 2 HP @480V, 2 HP @600V
  • Voltage Rating V: 600
  • Number of Phases: 3
  • NEMA Size: 00
  • Overload Range A: FH heater elements ordered separately (V5-T2-136/137)
  • Overload Class: Class 20 (Type B, manual reset)
  • Coil Voltage: 480V 60Hz
  • Enclosure Type NEMA: Open
  • Reversing: No

Applications

Ideal for pumps, fans, compressors, conveyors and general motor control in industrial plants, commercial buildings, water and wastewater facilities and OEM equipment.

Request a Quote