XTAE150G00WD035 IEC Frame G 150A Non Reversing Starter 25 to 35

Part Number:
Warranty:
In Stock
Available
Part Number
XTAE150G00WD035
Manufacturer
Eaton
Current Rating
150
Voltage Rating (V)
690
Number of Poles
3
Standards Compliance
UL 60947 to 4-1, CSA C22.2 No. 60947 to 4-1, IEC/EN 60947 to 4-1, CE
UL Listed
Yes
Starter Type
IEC full voltage non reversing magnetic starter: XTCE contactor + XTOB bimetallic overload relay (factory assembled)
HP Rating
15 HP 1 ph 115V; 30 HP 1 ph 230V; 40 HP 3 ph 200V; 60 HP 3 ph 230V; 125 HP 3 ph 460V; 125 HP 3 ph 575V
Voltage Rating V
690 (UL 600)
Number of Phases
3
NEMA Size
Not NEMA sized IEC frame G (90 mm)
Overload Range A
25 to 35
Overload Class
Class 10A
Coil Voltage
WD = 48 to 60Vdc
Contact Configuration
3NO main
Enclosure Type NEMA
Open (IP20)
Reversing
No
Disconnect Included; Short Circuit Protection
No; Not included provide fuses or circuit breaker per NEC/CEC (see Type 2 coordination tables V5 T1 to 237+)
Standards Compliance
UL 60947 to 4-1, CSA C22.2 No. 60947 to 4-1, IEC/EN 60947 to 4-1, CE
Application Use Case
Industrial motor control: pumps, fans, compressors, conveyors, machine tools and OEM panels
Special Features
XTOB bimetallic overload, phase loss sensitive

Eaton XT XTAE150G00WD035 IEC Frame G 150A Non Reversing Starter 25 to 35A XTOB Overload 48 to 60Vdc Coil

The Eaton XT XTAE150G00WD035 IEC Frame G 150A Non Reversing Starter 25 to 35A XTOB Overload 48 to 60Vdc Coil is part of Eaton's XT XTAE IEC motor control line. Starter Type: IEC full voltage non reversing magnetic starter: XTCE contactor + XTOB bimetallic overload relay (factory assembled), HP Rating: 15 HP 1 ph 115V; 30 HP 1 ph 230V; 40 HP 3 ph 200V; 60 HP 3 ph 230V; 125 HP 3 ph 460V; 125 HP 3 ph 575V, Voltage Rating V: 690 (UL 600), Number of Phases: 3.

Key Features and Benefits

Factory assembled IEC starter with phase loss sensitive, ambient compensated XTOB overload, test/reset and selectable manual/auto reset.

Applications

Industrial motor control: pumps, fans, compressors, conveyors, machine tools and OEM panels.

Quality and Compliance

Designed to UL, CSA and IEC standards. Contact RS Breakers for pricing, availability and application support.