Square D PowerPact HDL26110C H-Frame 2P 110A MCCB Lug 100%

star
star
star
star
star

110A, 2-Pole, MCCB, 600V, 25kA IC, H-Frame, TMD

Product Code:
In Stock
Available
Part Number
HDL26110C
Manufacturer
Schneider Electric
Current Rating
110A
Voltage Rating (V)
600V AC / 250V DC
Number of Poles
2P
Weight
~5 lbs
Dimensions
5.90" H x 3.00" W x 3.63" D
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
UL Listed
Yes
Frame Size
150A
Rated Current
110A
Interrupting Capacity
25kA@240V, 18kA@480V, 14kA@600V
AIC Rating
14
Trip Type
Thermal-Magnetic (Fixed)
Trip Unit Model
TMD (Thermal-Magnetic)
Mounting Style
Unit Mount
Connection Type
Lug (Unit Mount)
Lug Configuration
AL150HD Lug
Current Limiting
No
HACR Rated
Yes
Wire Range
14-3/0 AWG Al/Cu
Ambient Temperature
40°C
Technical Specifications
Frame: H-Frame 150A | IC: 25kA@240V, 18kA@480V, 14kA@600V | Poles: 2 | Voltage: 600V AC / 250V DC | Trip: Thermal-Magnetic (Fixed) | Mount: Unit Mount | Connection: Lug (Unit Mount)
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
Application Use Case
Branch circuit protection, feeder protection, motor circuit protection, panelboard/switchboard applications, MCC installations
Special Features
Thermal-Magnetic (Fixed)

Square D PowerPact HDL26110C H-Frame 2P 110A MCCB Lug 100%

150A Frame | 110A | 2P | 25kA@240V, 18kA@480V, 14kA@600V | Thermal-Magnetic (Fixed)

Square D's PowerPact HDL26110C H-Frame circuit breaker provides 110A 2-pole circuit protection engineered for commercial and industrial electrical distribution systems. Featuring standard interrupting capacity rated at 25kA@240V, 18kA@480V, 14kA@600V and operating at 600V AC / 250V DC, this breaker delivers proven and reliable overcurrent protection performance. The HDL26110C incorporates a TMD (Thermal-Magnetic) trip unit for reliable overcurrent protection including thermal overload and magnetic instantaneous response capabilities. This proven trip technology provides fixed protection characteristics precisely optimized for the H-Frame platform, ensuring consistent and dependable circuit protection across a wide range of operating conditions and fault scenarios. The HDL26110C features unit mount configuration with lug (unit mount) connections and AL150HD Lug terminations for straightforward installation. Accepting 14-3/0 AWG Al/Cu conductors, this breaker measures 5.90" H x 3.00" W x 3.63" D and weighs ~5 lbs, providing a compact footprint for space-efficient installation in panelboards, switchboards, and motor control centers. Certified to UL 489, CSA, and IEC/EN 60947-2 international standards, the HDL26110C ensures compliance across diverse global markets and jurisdictions. This breaker serves commercial and industrial power distribution, feeder protection, motor circuit applications, and switchgear installations requiring dependable H-Frame frame interrupting performance. Backed by Schneider Electric's global expertise in power distribution solutions, the HDL26110C ensures dependable protection for critical electrical infrastructure with comprehensive factory warranty coverage and support.

Key Features

This PowerPact MCCB features Thermal-Magnetic (Fixed) trip protection rated 110A at 600V AC / 250V DC. Frame size: 150A. Interrupting capacity: 25kA@240V, 18kA@480V, 14kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.

Applications

Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.