Square D PowerPact HJL26015 H-Frame 2P 15A MCCB Lug 80%

star
star
star
star
star

15A, 2-Pole, MCCB, 600V, 100kA IC, H-Frame, TMD

Product Code:
In Stock
Available
Part Number
HJL26015
Manufacturer
Schneider Electric
Current Rating
15A
Voltage Rating (V)
600V AC / 250V DC
Number of Poles
2P
Weight
~5 lbs
Dimensions
5.90" H x 3.00" W x 3.63" D
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
UL Listed
Yes
Frame Size
150A
Rated Current
15A
Interrupting Capacity
100kA@240V, 65kA@480V, 25kA@600V
AIC Rating
25
Trip Type
Thermal-Magnetic (Fixed)
Trip Unit Model
TMD (Thermal-Magnetic)
Mounting Style
Unit Mount
Connection Type
Lug (Unit Mount)
Lug Configuration
AL150HD Lug
Current Limiting
Yes
HACR Rated
Yes
Wire Range
14-3/0 AWG Al/Cu
Ambient Temperature
40°C
Technical Specifications
Frame: H-Frame 150A | IC: 100kA@240V, 65kA@480V, 25kA@600V | Poles: 2 | Voltage: 600V AC / 250V DC | Trip: Thermal-Magnetic (Fixed) | Mount: Unit Mount | Connection: Lug (Unit Mount)
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
Application Use Case
Branch circuit protection, feeder protection, motor circuit protection, panelboard/switchboard applications, MCC installations
Special Features
Thermal-Magnetic (Fixed), Current Limiting

Square D PowerPact HJL26015 H-Frame 2P 15A MCCB Lug 80%

150A Frame | 15A | 2P | 100kA@240V, 65kA@480V, 25kA@600V | Thermal-Magnetic (Fixed)

Square D's PowerPact HJL26015 H-Frame circuit breaker provides 15A 2-pole circuit protection engineered for commercial and industrial electrical distribution systems. Featuring extra-high interrupting capacity rated at 100kA@240V, 65kA@480V, 25kA@600V and operating at 600V AC / 250V DC, this breaker delivers proven and reliable overcurrent protection performance. This breaker incorporates a factory-calibrated TMD (Thermal-Magnetic) trip unit providing both thermal overload and instantaneous magnetic short-circuit protection. The H-Frame platform's proven trip mechanism ensures reliable operation with consistent and repeatable protection characteristics for dependable circuit protection throughout the breaker's entire service life. The HJL26015 features unit mount configuration with lug (unit mount) connections and AL150HD Lug terminations for straightforward installation. Accepting 14-3/0 AWG Al/Cu conductors, this breaker measures 5.90" H x 3.00" W x 3.63" D and weighs ~5 lbs, providing a compact footprint for space-efficient installation in panelboards, switchboards, and motor control centers. Certified to UL 489, CSA, and IEC/EN 60947-2 international standards, the HJL26015 ensures compliance across diverse global markets and jurisdictions. This breaker serves commercial and industrial power distribution, feeder protection, motor circuit applications, and switchgear installations requiring dependable H-Frame frame interrupting performance. The HJL26015 exemplifies Schneider Electric's PowerPact platform engineering excellence, delivering consistent protection performance with robust construction designed for long service life in demanding environments.

Key Features

This PowerPact MCCB features Thermal-Magnetic (Fixed) trip protection rated 15A at 600V AC / 250V DC. Frame size: 150A. Interrupting capacity: 100kA@240V, 65kA@480V, 25kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.

Applications

Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.