Square D PowerPact HJL26025 H-Frame 2P 25A MCCB Lug 80%
150A Frame | 25A | 2P | 100kA@240V, 65kA@480V, 25kA@600V | Thermal-Magnetic (Fixed)
The PowerPact HJL26025 from Schneider Electric's Square D product line is a H-Frame 2-pole 25-amp circuit breaker designed for professional electrical installations and industrial systems. This MCCB delivers extra-high interrupting capacity of 100kA@240V, 65kA@480V, 25kA@600V at 600V AC / 250V DC for dependable overcurrent protection performance. Featuring a TMD (Thermal-Magnetic) trip unit, the HJL26025 delivers dependable thermal overload and magnetic short-circuit protection for continuous operation. The fixed trip characteristics are factory-calibrated for optimal protection performance, providing reliable overcurrent sensing and fast fault interruption across the full range of anticipated operating conditions. The HJL26025 features unit mount configuration with lug (unit mount) connections and AL150HD Lug terminations for straightforward installation. Accepting 14-3/0 AWG Al/Cu conductors, this breaker measures 5.90" H x 3.00" W x 3.63" D and weighs ~5 lbs, providing a compact footprint for space-efficient installation in panelboards, switchboards, and motor control centers. UL 489 listed and CSA C22.2 No.5 certified, the HJL26025 meets IEC/EN 60947-2 international standards for global project specification and acceptance. Applications include feeder circuit protection, branch circuit protection, motor control center installations, panelboard and switchboard applications, and industrial power distribution systems requiring H-Frame frame-class protection capabilities. The PowerPact HJL26025 represents Schneider Electric's commitment to electrical safety, performance, and reliability in power distribution equipment for professional electrical installations worldwide.
Key Features
This PowerPact MCCB features Thermal-Magnetic (Fixed) trip protection rated 25A at 600V AC / 250V DC. Frame size: 150A. Interrupting capacity: 100kA@240V, 65kA@480V, 25kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.
Applications
Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.