flash_on
100% Canadian Owned and Operated – Shipping across Canada and America – 24*7 Emergency Services
flash_on
100% Canadian Owned and Operated – Shipping across Canada and America – 24*7 Emergency Services
flash_on
100% Canadian Owned and Operated – Shipping across Canada and America – 24*7 Emergency Services
flash_on
100% Canadian Owned and Operated – Shipping across Canada and America – 24*7 Emergency Services
flash_on
100% Canadian Owned and Operated – Shipping across Canada and America – 24*7 Emergency Services

Square D PowerPact HJL36090 H-Frame 3P 90A MCCB Lug 80%

star
star
star
star
star

90A, 3-Pole, MCCB, 600V, 100kA IC, H-Frame, TMD

Product Code:
In Stock
Available
Part Number
HJL36090
Manufacturer
Schneider Electric
Current Rating
90A
Voltage Rating (V)
600V AC / 250V DC
Number of Poles
3P
Weight
~7 lbs
Dimensions
5.90" H x 4.50" W x 3.63" D
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
UL Listed
Yes
Frame Size
150A
Rated Current
90A
Interrupting Capacity
100kA@240V, 65kA@480V, 25kA@600V
AIC Rating
25
Trip Type
Thermal-Magnetic (Fixed)
Trip Unit Model
TMD (Thermal-Magnetic)
Mounting Style
Unit Mount
Connection Type
Lug (Unit Mount)
Lug Configuration
AL150HD Lug
Current Limiting
Yes
HACR Rated
Yes
Wire Range
14-3/0 AWG Al/Cu
Ambient Temperature
40°C
Technical Specifications
Frame: H-Frame 150A | IC: 100kA@240V, 65kA@480V, 25kA@600V | Poles: 3 | Voltage: 600V AC / 250V DC | Trip: Thermal-Magnetic (Fixed) | Mount: Unit Mount | Connection: Lug (Unit Mount)
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
Application Use Case
Branch circuit protection, feeder protection, motor circuit protection, panelboard/switchboard applications, MCC installations
Special Features
Thermal-Magnetic (Fixed), Current Limiting

Square D PowerPact HJL36090 H-Frame 3P 90A MCCB Lug 80%

150A Frame | 90A | 3P | 100kA@240V, 65kA@480V, 25kA@600V | Thermal-Magnetic (Fixed)

The PowerPact HJL36090 from Schneider Electric's Square D product line is a H-Frame 3-pole 90-amp circuit breaker designed for professional electrical installations and industrial systems. This MCCB delivers extra-high interrupting capacity of 100kA@240V, 65kA@480V, 25kA@600V at 600V AC / 250V DC for dependable overcurrent protection performance. This breaker incorporates a factory-calibrated TMD (Thermal-Magnetic) trip unit providing both thermal overload and instantaneous magnetic short-circuit protection. The H-Frame platform's proven trip mechanism ensures reliable operation with consistent and repeatable protection characteristics for dependable circuit protection throughout the breaker's entire service life. The HJL36090 features unit mount configuration with lug (unit mount) connections and AL150HD Lug terminations for straightforward installation. Accepting 14-3/0 AWG Al/Cu conductors, this breaker measures 5.90" H x 4.50" W x 3.63" D and weighs ~7 lbs, providing a compact footprint for space-efficient installation in panelboards, switchboards, and motor control centers. Certified to UL 489, CSA, and IEC/EN 60947-2 international standards, the HJL36090 ensures compliance across diverse global markets and jurisdictions. This breaker serves commercial and industrial power distribution, feeder protection, motor circuit applications, and switchgear installations requiring dependable H-Frame frame interrupting performance. The HJL36090 exemplifies Schneider Electric's PowerPact platform engineering excellence, delivering consistent protection performance with robust construction designed for long service life in demanding environments.

Key Features

This PowerPact MCCB features Thermal-Magnetic (Fixed) trip protection rated 90A at 600V AC / 250V DC. Frame size: 150A. Interrupting capacity: 100kA@240V, 65kA@480V, 25kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.

Applications

Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.