Square D PowerPact JRL36250M75 J-Frame 3P 250A MCP

star
star
star
star
star

250A, 3-Pole, MCP, 600V, 200kA IC, J-Frame, MCP M75

Product Code:
In Stock
Available
Part Number
JRL36250M75
Manufacturer
Schneider Electric
Current Rating
250A
Voltage Rating (V)
600V AC
Number of Poles
3P
Weight
~12 lbs
Dimensions
5.90" H x 4.50" W x 3.63" D
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
UL Listed
Yes
Frame Size
250A
Rated Current
250A
Interrupting Capacity
200kA@240V, 200kA@480V, 100kA@600V
AIC Rating
100
Trip Type
Motor Circuit Protector
Trip Unit Model
MCP M75
Mounting Style
Unit Mount
Connection Type
Lug (Unit Mount)
Lug Configuration
AL250JD Lug
Current Limiting
Yes
Wire Range
3/0-350 kcmil Al/Cu
Ambient Temperature
40°C
Technical Specifications
Frame: J-Frame 250A | IC: 200kA@240V, 200kA@480V, 100kA@600V | Poles: 3 | Voltage: 600V AC | Trip: Motor Circuit Protector | Mount: Unit Mount | Connection: Lug (Unit Mount)
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
Application Use Case
Motor branch circuit protection, combination starters, motor control centers, OEM equipment
Special Features
Motor Circuit Protector, Current Limiting

Square D PowerPact JRL36250M75 J-Frame 3P 250A MCP

250A Frame | 250A | 3P | 200kA@240V, 200kA@480V, 100kA@600V | Motor Circuit Protector

The Schneider Electric Square D PowerPact JRL36250M75 is a J-Frame motor circuit protector providing 250-ampere 3-pole motor branch circuit protection for demanding industrial applications. This specialized MCP operates at 600V AC and delivers extreme interrupting capacity rated at 200kA@240V, 200kA@480V, 100kA@600V, ensuring reliable motor circuit coordination. Equipped with a magnetic-only trip unit, this motor circuit protector provides instantaneous short-circuit protection for motor branch circuits per NEC Article 430 requirements. The adjustable magnetic trip setting allows precise coordination with motor starter overload relays for complete motor branch circuit protection in industrial and commercial applications. This unit mount breaker features lug (unit mount) connections with AL250JD Lug terminations, accepting 3/0-350 kcmil Al/Cu conductors for versatile wiring applications. With overall dimensions of 5.90" H x 4.50" W x 3.63" D and weighing ~12 lbs, the JRL36250M75 delivers J-Frame frame protection in a space-efficient package suitable for dense electrical equipment layouts. UL 489 listed and CSA certified with IEC/EN 60947-2 compliance, the JRL36250M75 meets international standards for motor circuit protection applications. Ideal for industrial motor control centers, combination motor starters, OEM equipment, and HVAC systems requiring dedicated motor branch circuit short-circuit protection. The JRL36250M75 exemplifies Schneider Electric's PowerPact platform engineering excellence, delivering consistent protection performance with robust construction designed for long service life in demanding environments.

Key Features

This PowerPact MCCB features Motor Circuit Protector trip protection rated 250A at 600V AC. Frame size: 250A. Interrupting capacity: 200kA@240V, 200kA@480V, 100kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.

Applications

Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.