Square D PowerPact LDL34600WU53X L-Frame 3P 600A Mission Critical UM
600A Frame | 600A | 3P | 25kA@240V, 18kA@480V, 14kA@600V | Electronic Mission Critical (MicroLogic 5.3E LSI)
The Schneider Electric Square D PowerPact LDL34600WU53X is a L-Frame molded case circuit breaker rated at 600 amperes for 3-pole applications in commercial and industrial power distribution systems. This premium breaker delivers standard interrupting capacity rated at 25kA@240V, 18kA@480V, 14kA@600V, operating at 480Y/277V AC for reliable overcurrent protection in critical electrical infrastructure. The LDL34600WU53X features a MicroLogic 5.3E LSI electronic trip unit providing adjustable long-time delay, short-time delay, instantaneous, and ground fault protection settings for precise overcurrent coordination. This advanced electronic trip technology enables optimized protection curves, selective coordination with upstream and downstream protective devices, and significantly enhanced system reliability. The LDL34600WU53X features unit mount configuration with lug (unit mount) connections and AL400L61K3/AL600LS52K3 terminations for straightforward installation. Accepting (2) 2/0-500 kcmil Al/Cu conductors, this breaker measures 10.24" H x 5.51" W x 5.67" D and weighs ~25 lbs, providing a compact footprint for space-efficient installation in panelboards, switchboards, and motor control centers. Compliant with UL 489, CSA C22.2 No.5, and IEC/EN 60947-2 international standards, the LDL34600WU53X carries multiple certifications for worldwide acceptance and specification. Ideal for commercial buildings, industrial facilities, data centers, healthcare facilities, and critical infrastructure power distribution requiring reliable 600A 3-pole overcurrent protection. Backed by Schneider Electric's global expertise in power distribution solutions, the LDL34600WU53X ensures dependable protection for critical electrical infrastructure with comprehensive factory warranty coverage and support.
Key Features
This PowerPact MCCB features Electronic Mission Critical (MicroLogic 5.3E LSI) trip protection rated 600A at 480Y/277V AC. Frame size: 600A. Interrupting capacity: 25kA@240V, 18kA@480V, 14kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.
Applications
Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.