Square D PowerPact LGL36600TU44X L-Frame 3P 600A Field-Interch Electronic 80%
600A Frame | 600A | 3P | 65kA@240V, 35kA@480V, 18kA@600V | Electronic Field-Interch (MicroLogic 6.3A LSIG)
The Schneider Electric Square D PowerPact LGL36600TU44X is a L-Frame molded case circuit breaker rated at 600 amperes for 3-pole applications in commercial and industrial power distribution systems. This premium breaker delivers high interrupting capacity rated at 65kA@240V, 35kA@480V, 18kA@600V, operating at 600V AC for reliable overcurrent protection in critical electrical infrastructure. The LGL36600TU44X features a MicroLogic 6.3A LSIG electronic trip unit providing adjustable long-time delay, short-time delay, instantaneous, and ground fault protection settings for precise overcurrent coordination. This advanced electronic trip technology enables optimized protection curves, selective coordination with upstream and downstream protective devices, and significantly enhanced system reliability. This unit mount breaker features lug (unit mount) connections with AL400L61K3/AL600LS52K3 terminations, accepting (2) 2/0-500 kcmil Al/Cu conductors for versatile wiring applications. With overall dimensions of 10.24" H x 5.51" W x 5.67" D and weighing ~25 lbs, the LGL36600TU44X delivers L-Frame frame protection in a space-efficient package suitable for dense electrical equipment layouts. Certified to UL 489, CSA, and IEC/EN 60947-2 international standards, the LGL36600TU44X ensures compliance across diverse global markets and jurisdictions. This breaker serves commercial and industrial power distribution, feeder protection, motor circuit applications, and switchgear installations requiring dependable L-Frame frame interrupting performance. The LGL36600TU44X exemplifies Schneider Electric's PowerPact platform engineering excellence, delivering consistent protection performance with robust construction designed for long service life in demanding environments.
Key Features
This PowerPact MCCB features Electronic Field-Interch (MicroLogic 6.3A LSIG) trip protection rated 600A at 600V AC. Frame size: 600A. Interrupting capacity: 65kA@240V, 35kA@480V, 18kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.
Applications
Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.