Square D PowerPact LGL44600WU44X L-Frame 4P 600A Mission Critical UM

star
star
star
star
star

600A, 4-Pole, MCCB, 277V, 65kA IC, L-Frame, MicroLogic 6.3A

Product Code:
In Stock
Available
Part Number
LGL44600WU44X
Manufacturer
Schneider Electric
Current Rating
600A
Voltage Rating (V)
480Y/277V AC
Number of Poles
4P
Weight
~30 lbs
Dimensions
10.24" H x 7.09" W x 5.67" D
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
UL Listed
Yes
Frame Size
600A
Rated Current
600A
Interrupting Capacity
65kA@240V, 35kA@480V, 18kA@600V
AIC Rating
18
Trip Type
Electronic Mission Critical (MicroLogic 6.3A LSIG)
Trip Unit Model
MicroLogic 6.3A LSIG
Mounting Style
Unit Mount
Connection Type
Lug (Unit Mount)
Lug Configuration
AL400L61K4/AL600LS52K4
Current Limiting
No
Wire Range
(2) 2/0-500 kcmil Al/Cu
Ambient Temperature
40°C
Technical Specifications
Frame: L-Frame 600A | IC: 65kA@240V, 35kA@480V, 18kA@600V | Poles: 4 | Voltage: 480Y/277V AC | Trip: Electronic Mission Critical (MicroLogic 6.3A LSIG) | Mount: Unit Mount | Connection: Lug (Unit Mount)
Standards Compliance
UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE
Application Use Case
Branch circuit protection, feeder protection, motor circuit protection, panelboard/switchboard applications, MCC installations
Special Features
Electronic Mission Critical (MicroLogic 6.3A LSIG)

Square D PowerPact LGL44600WU44X L-Frame 4P 600A Mission Critical UM

600A Frame | 600A | 4P | 65kA@240V, 35kA@480V, 18kA@600V | Electronic Mission Critical (MicroLogic 6.3A LSIG)

Square D's PowerPact LGL44600WU44X L-Frame circuit breaker provides 600A 4-pole circuit protection engineered for commercial and industrial electrical distribution systems. Featuring high interrupting capacity rated at 65kA@240V, 35kA@480V, 18kA@600V and operating at 480Y/277V AC, this breaker delivers proven and reliable overcurrent protection performance. The LGL44600WU44X features a MicroLogic 6.3A LSIG electronic trip unit providing adjustable long-time delay, short-time delay, instantaneous, and ground fault protection settings for precise overcurrent coordination. This advanced electronic trip technology enables optimized protection curves, selective coordination with upstream and downstream protective devices, and significantly enhanced system reliability. Configured for unit mount installation, the LGL44600WU44X utilizes lug (unit mount) connections with AL400L61K4/AL600LS52K4 terminations designed for reliable conductor termination. The unit accommodates (2) 2/0-500 kcmil Al/Cu conductors within compact overall dimensions of 10.24" H x 7.09" W x 5.67" D weighing ~30 lbs, optimizing installation density in electrical distribution equipment. UL 489 listed and CSA C22.2 No.5 certified, the LGL44600WU44X meets IEC/EN 60947-2 international standards for global project specification and acceptance. Applications include feeder circuit protection, branch circuit protection, motor control center installations, panelboard and switchboard applications, and industrial power distribution systems requiring L-Frame frame-class protection capabilities. The LGL44600WU44X exemplifies Schneider Electric's PowerPact platform engineering excellence, delivering consistent protection performance with robust construction designed for long service life in demanding environments.

Key Features

This PowerPact MCCB features Electronic Mission Critical (MicroLogic 6.3A LSIG) trip protection rated 600A at 480Y/277V AC. Frame size: 600A. Interrupting capacity: 65kA@240V, 35kA@480V, 18kA@600V. Designed for reliable overcurrent protection in industrial and commercial power distribution systems.

Applications

Suitable for main distribution panels, motor control centers, switchboards, and feeder circuit protection in industrial facilities, data centers, and commercial buildings. Compliant with UL 489, CSA C22.2 No.5, IEC/EN 60947-2, NOM, CCC, CE.